作 者:张琦雪[1] 徐峰[1] 闫伟[1] 陈佳胜[1] 严伟[1]
机构地区:[1]南京南瑞继保电气有限公司,江苏省南京市211106
出 处:《电力系统自动化》2008年第24期96-99,共4页Automation of Electric Power Systems
摘 要:乒乓式或注入式发电机转子接地保护的二次回路需接到转子绕组的正负两端。600MW及以上容量的大型发电机的额定励磁电压普遍较高,且运行中会有各种过电压,因而担心二次回路绝缘等级偏低,不能承受足够的过电压。分析了在差模和共模电压作用下及转子绕组发生一点接地故障时,二次回路可能出现的严重过电压。研究结果表明,直接和间接与转子绕组相连接的二次回路电缆的耐压要求不同,宜采用独立的注入式转子一点接地保护并就地安装在励磁系统屏柜内,缩短直接与转子绕组连接的二次回路电缆;转子电压的信号采集宜采用具有隔离作用的变送器。Two schemes of generator rotor earth fault protection (REFP), named "ping-pong" and "voltage injection", are often applied. The secondary circuit of the REFP must be connected to the positive and negative terminals of rotor field windings. The rated field voltage of 600 MW or larger generator is commonly higher, and there are various over-voltages in the process of operation. Therefore, it is worried that the low-level insulation of the secondary circuit cannot withstand over-voltages. The over-voltages in the secondary circuit under the effects of common-mode and differential-mode voltages, while one-point rotor earth fault occurs, are analyzed. The results show that the demands on voltage withstanding capability of the secondary circuits, which are directly and non-directly connected to rotor field windings, are different. It suggests installing an independent relay of REFP in the cabinet of excitation system, so that the length of the directly connecting secondary circuit can be shortened. It is proper to use a transducer with galvanic insulation to measure the field voltage.
关 键 词:发电机 转子接地故障 继电保护 过电压 二次回路
分 类 号:TM862[电气工程—高电压与绝缘技术]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.117