不同换热形式的污水热泵工程运行能效分析  被引量:5

Analysis on Coefficients of Performance of Two Sewage-source Heat Pump Projects with Different Heat Exchange Modes

在线阅读下载全文

作  者:李建兴[1] 赵力[2] 池勇志[3] 

机构地区:[1]天津市市政工程设计研究院,天津300051 [2]天津大学机械工程学院,天津300072 [3]天津城市建设学院市政与环境工程系,天津300384

出  处:《中国给水排水》2009年第2期98-101,共4页China Water & Wastewater

摘  要:对分别采用直接式、间接式换热系统的两个不同的污水源热泵工程,进行了系统运行参数实测,并计算得到了冬季热泵系统的运行能效比。数据对比表明,直接换热式污水热泵系统的能效比较高,实际工况与样本工况的COP值偏差仅为7%,而间接式系统则为27%。The operation parameters of two sewage-source heat pump projects with direct and indirect heat exchange modes were measured, and the coefficients of performance (COP) of the heat pump systems in winter were calculated. The data comparison shows that the COP of the heat pump system with direct heat exchange mode is higher than that of the heat pump system with indirect heat exchange mode. For the direct heat exchange mode, the deviation of COP between the actual condition and the standard condition is 7% , while for the indirect one, it is 27%.

关 键 词:污水源热泵 直接换热 间接换热 运行特性 

分 类 号:X703.1[环境科学与工程—环境工程]

 