检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]华北电力大学电气与电子工程学院,北京102206 [2]杭州供电局,浙江杭州310018
出 处:《广西电力》2008年第6期10-13,24,共5页Guangxi Electric Power
摘 要:分析了小电流接地系统发生单相接地故障时的暂态故障特征,指出了传统小波选线方法的优点和需要改进的地方,提出了一种新型的自适应小波选线方法。该方法定义了2个衡量反映小波分解后各个尺度信息优劣的指标:绝对幅值强度和平均幅值强度,基于这2个指标,该方法能够自适应地选择分解尺度,提高选线结果的正确性。对仿真结果的分析表明了该方法的有效性和可行性。The transient fault characters of tingle-line-to-ground fault in no-direct-ground system are analyzed. The merits and demerits of traditional wavelet methods for fault line selection in no-direct-ground system are summarized and a new self-adaptive wavelet method is proposed. Two indices: absolute amplitude value and average amplitude value are defined to evaluate the nature of different scales of wavelet decomposition. Based on these indices, the proposed method can self-adaptively select decomposition scale and thus increase the correct rate offault line selection. The simulation result shows that the proposed method is effective.
分 类 号:TM711[电气工程—电力系统及自动化]