检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]哈尔滨理工大学电气与电子工程学院,哈尔滨150040
出 处:《电工技术学报》2008年第12期42-47,共6页Transactions of China Electrotechnical Society
基 金:国家自然科学基金资助项目(50577012)
摘 要:文中用直接相量法建立了能量变换器定子绕组内部故障分析的数学模型。该模型不仅可以对能量变换器中性点经高阻接地和经消弧线圈接地情况进行仿真,还能对绕组内部不同位置处发生的故障进行仿真。以一台能量变换器样机为模型,仿真了定子内部发生单相接地、两相接地故障情况,并给出了故障电流波形。与同容量的常规发电机相比,能量变换器的故障电流较小。In this paper mathematical models for simulating internal faults in powerformer, using direct phasor method, are described. Internal faults are simulated when the generator neutral point is either high resistance grounding or arc-suppression coil grounding. Simulations are also performed when a internal fault occurred at different locations along the winding. Simulation models during single phase-to-ground fault and two phase-to-ground fault are established by a powerformer prototype, and results about the fault currents are given. The fault current (p.u.) of powerformer is much smaller than th.e same capacity conventional generator.