220kV同塔双回输电线路雷击跳闸原因分析  被引量:11

Analysis on Lightning Stroke Tripping of 220 kV Double Circuit Transmission Lines on the Same Tower

在线阅读下载全文

作  者:金祖山[1] 吴健儿[2] 

机构地区:[1]浙江省电力试验研究院,杭州310014 [2]杭州市电力局,杭州310009

出  处:《浙江电力》2009年第1期51-53,共3页Zhejiang Electric Power

摘  要:雷击有可能造成双回线甚至多回线同时跳闸,对系统产生较大的冲击。结合某220kV同塔双回输电线路自投运以来多次发生同时雷击跳闸的情况,分析了历次雷击跳闸的原因和种类,提出了防止同塔双回输电线路雷击跳闸的措施。Lightning stroke maybe induce double or more circuit transmission lines on the same tower to trip simul- taneously, strike the power system badly. According to the operation experiences of lightning stroke tripping of 220 kV double circuit transmission lines on the same tower in a mountainous area of Zhejiang Province, the reasons and kinds of lightning stroke tripping every time are analyzed in the paper. Measures for preventing 220 kV double or more circuit transmission lines being tripped at the same time by lightning stroke are presented.

关 键 词:220 KV 同塔双回 输电线路 雷击 原因 

分 类 号:TM75[电气工程—电力系统及自动化]

 