河南电网500kV姚邵线舞动事故分析与治理措施  被引量:7

Analysis of He’nan Grid’s 500kV Yao-Shao Line Gallop Accident and Its Control

在线阅读下载全文

作  者:张天光 孙东海[2] 敖清诚 李本良 赵江涛 

机构地区:[1]河南省电力勘测设计院,郑州市450007 [2]河南省电力公司,郑州市450052

出  处:《电力建设》2009年第3期24-27,共4页Electric Power Construction

摘  要:河南电网500kV姚邵线2008年元月发生舞动倒塔事故。通过分析认为,恶劣天气引发的长时间导线持续舞动是导致事故的原因,由于导线长时间持续舞动,而塔身防盗螺母不能防松,导致螺栓松动脱落,进而导致铁塔辅助材脱落,铁塔结构体系变化最终引发事故。针对此情况,在姚邵线加装双摆稳定器和整个塔身横担以下防盗螺栓加装螺栓防松帽,以提高塔身的抗舞能力。Jan. 2008, conductor gallop induced tower collapse occurred in Henan grid's 500 kV Yao-Shao Line. Analysis suggest that the accident is caused by the foul weather induced continuous conductor gallop over a long period, resulting in loose bolts on the tower and causing secondary members falling off. The structural change finally caused the accident. Based on this, double pendulum stabilizer and self-locking nuts were installed in Yao-Shao Line to improve tower anti-gallop capability.

关 键 词:500kV姚邵线 导线舞动 事故分析 防舞治理措施 

分 类 号:TM752[电气工程—电力系统及自动化]

 