热泵型空调系统制冷剂流量控制方法的研究  被引量:8

Study of refrigerant flow rate control methods in a heat pump air conditioning system

在线阅读下载全文

作  者:苏顺玉[1] 张春枝[1] 陈俭[1] 

机构地区:[1]武汉科技大学

出  处:《暖通空调》2009年第3期128-130,共3页Heating Ventilating & Air Conditioning

基  金:湖北省自然科学基金资助项目(编号:2008CDB363)

摘  要:以Harms模型计算两相区内的空泡系数,用稳态分布参数法计算了制冷和制热两种运行工况下热泵型空调系统冷凝器和蒸发器内所含的制冷剂量。结果表明,制热工况下的制冷剂充注量比制冷工况下的充注量小。在此基础上提出了储液器法和喷射液态制冷剂法两种制冷剂流量控制方法。Calculates the void fraction in two-phase fluid region by Harms model, and calculates the refrigerant charge quantity in the condenser and evaporator in a heat pump air conditioning system with steady distributed parameter method under refrigeration and heating operating situations. The results show that refrigerant charge quantity in heating operating condition is less than that in refrigeration operating condition. Presents the two refrigerant flow rate control methods of liquid reservoir and ejecting liquid refrigerant based on above investigation.

关 键 词:Harms模型 制冷剂充注量 储液器 喷射 

分 类 号:TU831.3[建筑科学—供热、供燃气、通风及空调工程] U463.851[机械工程—车辆工程]

 