降低逆变器容量的混合有源电力滤波器控制方式  被引量:3

Control Methods of Hybrid Active Power Filter Reduced Its Converter Rating

在线阅读下载全文

作  者:陈峻岭[1] 李耀华[1] 姜新建[2] 朱东起[2] 

机构地区:[1]中国科学院电工研究所,北京100190 [2]清华大学电机系,北京100084

出  处:《电工技术学报》2009年第4期214-218,共5页Transactions of China Electrotechnical Society

摘  要:针对一种降低逆变器容量的混合有源电力滤波器,详细介绍了其在三种控制方式下的工作原理、性能特点和等效电路,搭建了容量为10kV.A的混合有源电力滤波器实验样机,并进行了三种控制方式的实验和分析。实验结果表明,采用复合控制方式,该结构中逆变器容量仅为整个滤波器容量的4.42%,而该滤波器投入后,电网电流总谐波畸变率从26.95%下降到4.25%,补偿效果良好且优于其他两种控制方式。This paper presents three control methods for a hybrid active power filter (HAPF) , which is reduced the rating of its converter. Their principles, filtering performances and equivalent circuits of the HAPF are discussed in detail. Experiment waveforms are obtained in a laboratory prototype, rated at 10kVA. Experiment results prove the converter rating accounts for only 4.42% of the HAPF rating while the total harmonic distortion (THD) of the system current is reduced to 4.25% from 26.95% using the combined control method, which is better than the other control methods.

关 键 词:谐波 混合有源电力滤波器 基波谐振支路 控制方式 

分 类 号:TM761[电气工程—电力系统及自动化]

 