作 者:江道灼[1] 金鑫[1] 杨贵玉[1] 吴文宣[2] 陈金祥[2]
机构地区:[1]浙江大学电气工程学院,浙江省杭州市310027 [2]福建电力试验研究院,福建省福州市350007
出 处:《电力系统自动化》2009年第9期77-80,99,共5页Automation of Electric Power Systems
摘 要:探讨了中性点接地三相桥式固态限流器桥路故障诊断方法。仿真研究表明,通过监测、分析桥路直流电感电流和2个续流管电流,能够有效区分不同类型的桥臂开断与直通故障,实现对桥路故障类型的诊断;通过对桥路直流电感电流波形和2个续流管电流波形及其傅里叶变换分析,可计算出直流分量、基波分量和二次谐波分量,根据其数值特点,实现对故障桥臂的定位。该方法具有监测量小、故障特征明显、判据简单等特点,可用于在线监测、诊断固态限流器整流桥桥臂故障。This paper presents a fault diagnosis method for neutral grounding three-phase bridge type solid-state fault current limiter (SSFCL). Simulation studies show that based on monitoring and analysis of current of DC reactor and two free-wheeling diodes for the bridge, different type faults of bridge-arm breaking and through can be effectively distinguished so as to implement diagnosis of bridge fault type. With current waveforms of the DC reactor and two free-wheeling diodes and their Fourier analysis, the DC, fundamental and second harmonic components can be calculated to locate fault bridge-arm. This method has many advantages, such as small monitoring amount, obviousness of fault characteristic, the simple criterion, etc. It is conducive to realize on-line monitoring and fault diagnosis for arms of rectifier bridge of SSFCL.
关 键 词:中性点接地 三相桥式固态限流器 桥臂故障诊断 傅里叶变换