电流互感器高压介损现场测量方法的研究  被引量:3

Study on Field Testing High Voltage Dielectric Loss of Current Transformer

在线阅读下载全文

作  者:李璠[1] 阎春雨[1] 陈香宇[2] 刘海峰[1] 

机构地区:[1]河北省电力研究院,河北石家庄050021 [2]石家庄供电公司,河北石家庄050051

出  处:《华北电力技术》2009年第5期14-16,50,共4页North China Electric Power

摘  要:针对电流互感器高压介损现场测量存在的问题,经过不断的实践、总结,提出电流互感器高压介损现场测量的新方法,即:三相被试互感器并联同时加压,小电抗器积木搭接进行串联补偿,激磁侧通过变频电源控制试验频率,避开现场干扰,在工频50 Hz两侧各测一个点,通过求平均值推算出50 Hz频率下的介损数据。According to the problems existed in field testing high voltage dielectric loss of current transformer, through constant practice and summary, this paper presented a new testing method, namely : parallel step-up to testing 3-phase transformer at the same time, lapping in building-block small reactors for series compensation, controlling test frequency by the power source with variable frequency at exciting side to avoid interference at the field,testing respectively a point on both sides of the industrial frequency of 50 Hz,to get dielectric loss data at the frequency of 50 Hz by calculating average value.

关 键 词:电流互感器 介损 变频电源 抗干扰 

分 类 号:TM452[电气工程—电器]

 