检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
出 处:《电测与仪表》2009年第5期32-35,56,共5页Electrical Measurement & Instrumentation
摘 要:三相三线并联有源电力滤波器能够实时的补偿谐波电流和无功电流。目前,并联有源电力滤波器的补偿原理大多是补偿电流跟踪检测出的参考谐波电流。在分析以往的补偿原理之后,提出了把检测出的谐波功率作为参考功率信号,然后,采用直接功率控制方法,设计有源电力滤波器的控制器,使滤波器的输出的谐波功率跟踪参考功率,从而达到消除谐波的目的。仿真试验结果表明,采用这种控制策略设计出的有源电力滤波器具有良好的谐波补偿效果。Three-phase three-line shunt Active Power Filter (APF) can be used to restrain harmonic currents and compensate reactive power current on-line. At present, most of the compensation principles of APF are that the compensation currents track the detected reference harmonic currents. After the analysis of the previous compensation principles, a novel control method is proposed in this paper that harmonic power is detected to be the reference compensation power firstly. Then, adopting Direct Power Control (DPC) method, an APF controller is designed to make compensation power track the reference compensation power, so as to achieve the purpose of eliminating harmonics. At the end, simulation results indicate that the APF based on DPC shows perfect harmonic compensation performances.
关 键 词:有源电力滤波器 直接功率控制 谐波抑制 瞬时功率理论
分 类 号:TM76[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:3.22.79.2