双馈风电机组接入地区电网后的电压稳定分析  被引量:25

Voltage Stability Analysis of Doubly Fed Induction Generator Wind Turbines Integration into Regional Power Grid

在线阅读下载全文

作  者:宋伟伟[1] 李强[1] 袁越[1] 

机构地区:[1]河海大学电气工程学院,南京210098

出  处:《电网与清洁能源》2009年第5期36-40,共5页Power System and Clean Energy

基  金:国高科技支撑计划(2008BAA141302);江苏省"青蓝工程"

摘  要:利用PSASP软件的UPI接口程序模块,在PSASP中建立了双馈风电机组模型,以两个实际的地区电网为例,研究双馈风电机组接入地区电网后对电网电压的影响,结果表明:双馈风电机组提高了地区电网的静态电压水平;双馈风电机组在故障后能够减少系统所需的无功储备,从而有利于地区电网的电压稳定;风速的波动对地区电网的电压有影响,但一般不会影响其暂态稳定性。Doubly fed induction generator (DFIG) model is established by the utilization of user program interface (UPI) program interface module in power system analysis software package (PSASP) software environment. Taking two actual regional power grids as an example, the impact of DFIG integration on regional power grid is studied in this paper. Simulation results clearly indicate that DFIG can strengthen the steady voltage level of regional power grid, and can reduce the needed reserve of reactive power after faults occurred, which can improve the voltage stability of regional power grid, the fluctuation of wind speed will affect the voltage of regional power grid, but usually do not affect the transient stability.

关 键 词:风力发电 电压稳定 双馈感应发电机组 PSASP 

分 类 号:TM315[电气工程—电机] TM712

 