由感应电压引起的电压异常原因分析与处理措施  被引量:6

Analysis of abnormal voltage due to induced voltage and related treatment measures

在线阅读下载全文

作  者:王健[1,2] 张嘉旻[3] 

机构地区:[1]华东电网有限公司电力调度中心,上海200002 [2]上海交通大学电子信息与电气工程学院,上海200240 [3]华东电力试验研究院有限公司,上海200437

出  处:《华东电力》2009年第5期880-882,共3页East China Electric Power

摘  要:针对外高桥三厂启动调试过程中导致断路器无法合闸的高感应电压现象,基于电磁暂态程序(EMTP)建立了外高桥三厂的感应电压分析模型,研究了外高桥三厂在各种工况下的桥引线感应电压,并提出了调度操作中应注意的问题和解决措施。The high induced vohage occurred during start-up debugging for Waigaoqiao No. 3 Power Plant made the circuit breaker unable to switch off. To solve the problem, the electromagnetic transient program (EMTP) was used to construct the induced voltage analysis model to investigate the induced voltage under various conditions for Waigao- qiao No. 3 Power Plant. Problems needing more attention were proposed, as well as countermeasures.

关 键 词:GIS 感应电压 EMTP 

分 类 号:TM711[电气工程—电力系统及自动化]

 