摘 要:配电变压器的微机保护是配电系统安全可靠运行的重要保证。针对配电变压器保护的复杂特点,提出了DSP与MCU复合的双CPU结构,DSP主要负责保护信号检测与保护运算,MCU主要负责测量信号检测与人机接口。改进了基于傅立叶变换的保护算法,采用增量式递推算法提高了检测的实时性,降低了算法的运算量。利用继电保护测试装置和模拟断路器进行了功能测试,结果表明该装置保护逻辑正确、动作灵敏可靠。The digital protection of power transformer is very important for the safe and reliable operation of power system. In the light of the complexity of power transformer protection, a protection device with double CPU of DSP and MCU is presented. The DSP completes protective signal sampling & protection calculation, and the MCU performs the electric measurement & man-machine iuterfacing. An improved protection algorithm based on recursive incremental Fourier transformation is applied to enhance real-time performance and reduce computational complexity. The functions of the device are tested with a standard relaying testing device and simulated circuit breaker, the results indicate that the relaying logic is correct and the protection operation is sensitive & reliable.