检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]清华大学电机工程与应用电子技术系,北京100084
出 处:《南方电网技术》2009年第4期15-19,共5页Southern Power System Technology
摘 要:以 Yd11 牵引变压器为例分析了不平衡电力系统多谐波源的传输特性,测试 4 种不同负载接入方式以揭示多谐波源之间的相互作用。采用 4 种不同的单相无源滤波器接入方案来补偿不平衡的谐波成分,得出当无源滤波器与非线性负载位于相同变电所同一相时具有最好的滤波效果,滤波后系统电流总谐波畸变率平均为 4.2%,当滤波器与非线性负载位于不同变电所,在相同相时具有较好的滤波效果,补偿后系统电流总谐波畸变率平均为 5.3%,但在不同相时会不同程度地放大谐波。The characteristics of multi-harmonic sources in unbalanced power system are analyzed with the Ydl 1 traction transformer of electrified railway as an example, and four types of connection mode were tested to illustrate the interaction among multi-harmonic sources. Four passive power filter schemes are adopted to compensate the unbalanced harmonic component, showing that the scheme with the power filter and the non-linear load being in the same substation and having the same phase has the best filtering effect as the total harmonic distortion of system current reducing to 4.2% averagely, and that with the filter and the non-linear load having the same phase but being in different substations has a good filtering effect as the total harmonic distortion of filtered current reducing to about 5.3%. Meanwhile, the schemes with the filter and the non-linear content of specific phase. load having different phases enlarge somehow the harmonic
关 键 词:不平衡系统 谐波传输特性 谐波抑制 总谐波畸变率
分 类 号:TM721.2[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.3