检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]大连理工大学 [2]大连天工设计有限公司
出 处:《暖通空调》2009年第11期83-87,共5页Heating Ventilating & Air Conditioning
基 金:国家自然科学基金资助项目(编号:50578049);"十一五"国家科技支撑计划资助课题(编号:2006BAJ01A09;2008BAJ12B05-05)
摘 要:分析和计算了程控机房间接利用室外冷源的关键设备空气冷却器的热工特性。结果显示,空气冷却器填料厚度越大,总换热量越大;淋水初温越低,相同换热量下的填料厚度越小;冷水温度每降低1℃所能减小的填料厚度仅为5 cm,相比于提高冷水进口温度经济效益不明显,一般可确定13℃为冷水进口温度。Analyses and calculates the thermal characteristics of the key equipment--air cooler for indirect free cooling tower used in communication rooms. The results show that the more stuffing height is, the more total heat exchange is, the less spray water temperature is, the less stuffing height is under the same heat exchange. When the temperature of cold water is decreased by 1 ℃, the stuffing height is decreased by merely 5 cm and it is not very significant compared with increased cold water temperature, and the inlet cold water temperature generally is determined as 13 ℃.
分 类 号:TU831.4[建筑科学—供热、供燃气、通风及空调工程]