检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
出 处:《电力系统保护与控制》2010年第2期122-123,130,共3页Power System Protection and Control
摘 要:阐述了电流互感器变比试验的必要性和特点,在简述了电流法、短路法测变压器套管CT变比试验的原理、特点以及主要缺点之后,提出了采用电压法不拆变压器套管CT测变压器套管CT变比试验的方法,分析了电压法测变压器套管CT变比试验的原理,试验时可能引起误差的主要因素。试验中采取的抗干扰措施,并在试验中采用伏安特性试验仪在套管CT二次侧加交流电压,测量一次侧电压和二次侧电压的方法,同时完成套管CT变比试验、伏安特性试验。This paper states the necessity and the characteristics of the current transformer ratio test ,reviews two normal methods of the CT ratio test in brief, i.e. short-circuit method and ctLrrent method. It brings forward new method of the CT ratio test by measuring voltage in primary side and secondary side of the CT without disassembling it, and analyzes the theory and the main factors causing errors of the new method. In the test, it adopts anti-interference method and applies AC voltage on secondary side of CT with I/V characteristic instrument to measure voltage of primary side and secondary side. The CT ratio test and IN characteristic test are carried out as well.
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:18.117.232.234