系统振荡时距离保护的对策  被引量:9

Scheme of the distance protection to avoid mal-operation in swing

在线阅读下载全文

作  者:李小滨[1] 刘凯[1,2] 陈巨升[1] 徐刚[1] 陈淑芝[1] 

机构地区:[1]东方电子股份有限公司,山东烟台264001 [2]西安交通大学电气工程学院,陕西西安710049

出  处:《电力系统保护与控制》2010年第3期86-89,共4页Power System Protection and Control

摘  要:通过对高压输电线路动模实验录波数据的分析,注意到振荡平息时,两侧电源之间的电势角度差有时会在180°左右停留一段较长的时间,这会导致目前常用的对称故障解锁方法失效,导致保护误动。针对这一情况,结合目前常用的振荡检测及解锁方法,提出了解决方法,通过两个电阻元件检测振荡速度,根据振荡速度实时地改变三相故障解锁判据的延时,较好地解决了这一问题。通过详尽的动模实验,验证了所提方法的有效性。Through the analysis of the dynamic model of HV transmission line recorded data, this paper points out that the angle between two source potentials of both sides of the line maybe remain as 180° for a relatively long time, which would fail the current swing block methods. A method is presented in this paper to solve such a problem, the swing speed is measured by the two resistance element real-timely, and the delay time of the swing unblock criterion is adjusted real-timely according to the real-time swing speed. The method is validated by the dynamic model data, simulation result shows that the presented method will not mal-operate during swing.

关 键 词:电力系统 输电线路 距离保护 振荡闭锁 故障开放 

分 类 号:TM773[电气工程—电力系统及自动化]

 