电力系统静态电压稳定与节点阻抗解析  

Static voltage stability and node impedance analysis in power systems

在线阅读下载全文

作  者:侯学勇[1] 鞠平[1] 史可琴 汤涌[3] 杨文宇 

机构地区:[1]河海大学能源与电气学院,江苏南京210098 [2]西北电网公司调度中心,陕西西安710000 [3]中国电力科学研究院,北京100085

出  处:《河海大学学报(自然科学版)》2010年第2期225-230,共6页Journal of Hohai University(Natural Sciences)

基  金:国家重点基础研究发展计划(973计划)(2004CB217901);国家杰出青年科学基金(50725723)

摘  要:通过一简单两节点系统,证明节点最大功率总是发生在节点负荷等值阻抗模与电源侧等效阻抗模相等的时候,而与负荷的功率因数无关,但负荷的功率因数决定临界功率的大小.分析PV曲线下半支稳定性及其与节点负荷等值阻抗模的关系,指出在以比较节点负荷等值阻抗模与临界阻抗模来判别系统电压稳定性时应考虑节点的负荷特性.Based on a simple two-node system, it was proved that the maximum power of nodes always occurred when the equivalent impedance module of the nodes was equal to that of the system. It was independent of the load power. However the critical power was dependent upon the load power. The stability of the low part of P-V curves as well as its relationship with the equivalent impedance module of loads was analyzed. A conclusion is drawn that the load characteristic should be considered when the voltage stability of power systems is evaluated by comparing the equivalent impedance module of nodes with their critical impedance module.

关 键 词:电力系统 电压稳定 等值阻抗模 PV曲线 负荷特性 

分 类 号:TM714.2[电气工程—电力系统及自动化]

 