电压互感器二次单相接地短路故障分析  被引量:9

Analysis on secondary single-phase grounding short circuit fault of voltage transformer

在线阅读下载全文

作  者:秦涛[1] 张磊[1] 王向东[1] 

机构地区:[1]银南供电局,宁夏吴忠751100

出  处:《电力系统保护与控制》2010年第7期136-138,共3页Power System Protection and Control

摘  要:针对电压互感器二次单相接地短路导致非故障相电压升高的情况,通过对电压二次电缆阻抗的测试,电压互感器接地点的改变等试验。分析、阐述了其产生的原因是二次电缆N相线芯阻抗在短路电流流过时产生电压叠加在非故障相线芯上所致。可采取增大N相线芯截面积或退出过电压保护等措施预防其对电网的不利影响。When single-phase of potemial transformer secondary winding grounds, it raises the voltage of the other two non-fault phases. By measuring the impedance of secondary voltage cable and changing the grounding points, this paper analyzes and expatiates the reason is that the N-phase current of secondary electric cable generates voltage to the other two non-fault phases when grounding current affluxes it. The ways of preventing its effection to electric network are extending the section of N-phase electric cable or blocking the overvoltage protection.

关 键 词:电压互感器 二次接地短路 分析 预防措施 

分 类 号:TM451[电气工程—电器]

 