检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:王晓蔚[1] 石振刚[1] 杨潇[1] 张倩茅[1]
出 处:《电气传动自动化》2010年第2期57-60,共4页Electric Drive Automation
摘 要:随着电网负荷和系统规模的增加,导致短路电流水平快速上升,因此对电网进行短路电流计算分析具有重大的意义。介绍了电力系统综合分析程序PSASP短路计算模块的主要功能,应用PSASP对某省500kV及220kV厂站的短路水平进行了全面计算与分析,针对部分厂站短路电流水平超标问题,提出了相应的措施和建议。并对规划2010年电磁环网解环后,500kV/220kV厂站的短路电流水平进行计算分析,计算结果为电网的安全运行提供了可靠依据。With the increase of loads and components in power grid,the sharp increase of short circuit current will be induced. So it is very important to carry out the analysis of short circuit calculation. The primary function of PSASP short circuit calculation is introduced. The general calculation of 500kV and 220kV station′s short circuit current in some province are carried out by PSASP. Because some stations′ short circuit current exceed the standard, the corresponding measures and suggestions are proposed. Finally, an analysis of 500kV and 220kV station′s short circuit current is carried out after opening the electromagnetic loop in 2010. These conclusions can provide reliable basis for the safty operation of power grid.
关 键 词:PSASP 短路计算 开关额定遮断电流 电磁解环
分 类 号:TM91[电气工程—电力电子与电力传动]