±500 kV宝鸡换流站交、直流滤波器调频调谐试验研究  被引量:4

Test & Research of AC & DC Filter Tuning Frequency Modulation in±500 kV Baoji Converter Station

在线阅读下载全文

作  者:王建波[1] 徐永正 尹俊钢[1] 薛建[1] 刘颖[1] 左宝峰[1] 

机构地区:[1]陕西电力科学研究院,陕西西安710054 [2]新疆伊犁电力有限责任公司,新疆伊犁835000

出  处:《陕西电力》2010年第3期34-37,共4页Shanxi Electric Power

摘  要:±500 kV宝鸡换流站是国家电网公司支援四川地震灾区的重点项目之一,文章详细介绍了该换流站交、直流滤波器调频调谐试验的全过程。首先依据滤波器的出厂参数通过软件仿真确定了谐振频率,参照相关调试标准确定了宝鸡换流站滤波器的调谐限值,再通过调节电抗器抽头并利用变频电源进行检测,最终使滤波器达到了设计要求。±500 kV Baoji Converter Station is one of the important project to supply assistance for Sichuan seismic disastrous area by State Grid Corporation.The whole test progress of AC DC filter toning frequency modulation in converter station is introduced.In accordance with the factory data of filter,resonant frequency is determined through software simulation.The tuning limited value of filter in Baoji converter station is determined as per related standard.Regulation the tap of reactor and check with variable-frequency power source have made the filter reach designed requirement.

关 键 词:换流站 滤波器 调频调谐试验 

分 类 号:TM631.3[电气工程—电力系统及自动化] TM531.5

 