检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]西南交通大学电气工程学院,四川成都610031 [2]国网电力科学研究院,江苏南京210061
出 处:《电力系统保护与控制》2010年第8期1-5,共5页Power System Protection and Control
基 金:教育部直属高校聘请外籍教师重点资助项目
摘 要:分析了线路电流差动保护中两端各补偿一半电容电流的传统补偿方法,指出该方法在区内故障时存在受故障点影响补偿不精确、降低灵敏度的缺点。提出了一种自适应电容电流补偿方法,在保证相同的区外故障可靠性基础上,大大提高了区内故障的灵敏度。对一条1000kV线路故障和电流差动保护进行了仿真试验,证明该自适应补偿方法的有效性和正确性,适合作为特高压输电线路电流差动保护电容电流补偿方法。The traditional capacitance current compensation is influenced by different fault locations and has lower sensitivity when internal faults occur in one end. An improved adaptive compensation scheme is proposed in this paper. The scheme combines the traditional compensation with compensation utilizing fault distance. The performances of two compensations are compared in the analytical way, showing that, when they have same security on external faults, the improved one has higher sensitivity when internal fault in one end. According to the simulations on the faults and the two compensations in a 1000 kV line, the results verify that the proposed method has achieved a great improvement on sensitivity of internal faults. It is a proper capacitance current compensation scheme for UHV transmission lines.
分 类 号:TM773[电气工程—电力系统及自动化]
正在载入数据...