贵州某35 kV变电站雷害事故分析与防雷改造  被引量:30

Analysis and Lightning Protection Reform Measures on Lighting Accident at a 35 kV Power Substation of Guizhou Province

在线阅读下载全文

作  者:申元[1] 李景禄[1] 彭利强[1] 邓文斌[1] 

机构地区:[1]长沙理工大学电气与信息工程学院,长沙410076

出  处:《电瓷避雷器》2010年第2期36-39,共4页Insulators and Surge Arresters

摘  要:针对贵州某35 kV变电站雷击事故,介绍了该变电站的防雷保护现状,从变电站直击雷保护,线路侵入波保护等方面分析了雷害事故发生的原因,提出了防雷害事故的整改措施:降低杆塔冲击接地电阻;完善进线段保护,降低雷电侵入波幅值和陡度;使用性能较好的金属氧化物避雷器代替普通阀型避雷器。通过以上整改,消除了该变电站防雷保护的薄弱环节,提高了供电可靠性。In view of the lighting accident at a lighting protection situation of the power substation 35 kV power substation of Guizhou Province , the is introduced, causes of lighting accident such as direct lighting protection and lighting intruding wave protection are analized. The measures such as reducing tower impulse grounding resistance, improving the incomingline protection to lower the amplitude and the slope of the lighting invasion wave, and better performance zinc oxide surge arresters are used instead of normal valve-type surge arrester. Through above rectification, the bottleneck of the substation lightning protection has been eliminated, the power supply reliability has been improved.

关 键 词:雷害事故 直击雷保护 雷电侵入波保护 接地电阻 防雷措施 

分 类 号:TM862[电气工程—高电压与绝缘技术]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象