辐射空调末端的分析与评价  被引量:10

Exergy Analysis and Evaluation of the Radiant Air Conditioning Terminal Device

在线阅读下载全文

作  者:隋学敏[1] 张旭[2] 

机构地区:[1]长安大学,陕西西安710054 [2]同济大学,上海200092

出  处:《流体机械》2010年第4期71-73,31,共4页Fluid Machinery

基  金:十一五国家科技支撑计划重大项目:长江流域住宅室内热湿环境低能耗控制技术研究与适范(2006BAJ01A05);现代建筑设计与施工关键技术研究(2006BAJ01B05)

摘  要:利用[火用]分析的方法,对辐射末端和普通风机盘管的[火用]效率进行比较,分析了辐射末端的节能率。结果表明设计工况下辐射末端[火用]效率为普通风机盘管的1.6~1.9倍,相对[火用]效率随着参考温度的升高而降低,随着辐射末端承担显热负荷比例的增加而增加。从能和质的节约角度出发,应尽量提高辐射末端承担的冷负荷比例。Using the method of exergy analysis, the exergy efficiency comparison between the radiant terminal device and the ordinary fan-coil is given, and the energy-saving potential of the radiant terminal device is analyzed. The results show that the exergy efficiency of the radiant terminal device is 1.6 - 1.9 times of the ordinary fan-coil. Ralative exergy efficiency reduces with the reference temperature rises, and increases with the sharing rate of sensible heat load of radiant terminal device increases. From the view of the saving of energy and quality, the sharing rate of sensible heat load of radiant terminal device should increase.

关 键 词:辐射末端 风机盘管 [火用]分析 相对炯效率 

分 类 号:TU831.31[建筑科学—供热、供燃气、通风及空调工程]

 