检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]保定供电公司,河北保定071000 [2]河北电力公司,河北石家庄050000
出 处:《高压电器》2010年第5期92-94,97,共4页High Voltage Apparatus
摘 要:总结了SF6开关设备气体渗漏的特点、现场表现及原因;讨论了解体除漏与带压堵漏的风险决策问题;介绍了泡沫法、定性检漏仪报警检漏法、包扎加定量检漏仪检漏法、激光成像检漏仪检漏法等常用检漏方法;阐述了检漏方法选择的观点;对带压堵漏进行了理论计算,介绍了几种漏点消除方法;最后介绍了几次现场检漏与漏点处理的典型案例。得出定性检漏仪和泡沫检漏法结合使用,操作简单,能提高检漏效率和成功率。This article summarized the SF6 switchgear gas leakage characteristics, the on-site performance and the reason; discussed the venture decision questions: the disintegration to eliminate leaks and the stoppage leaks with pressure; introduced the froth law, qualitative leak detector alarm leak detection law, the wrap add the quota leak detector leak detection law, the laser image formation leak detector law and so on the commonly used leak detection method; elaborated the leak detection method choice viewpoint; carried on the theoretical calculation of the stoppage leaks with pressure, introduced several leaking point elimination method; finally introduced several scene leak detection and the leaking point processing illustrative case.
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.38