机构地区:[1]东北电力大学,吉林吉林132012
出 处:《电力系统保护与控制》2010年第15期28-32,共5页Power System Protection and Control
摘 要:针对目前乒乓式励磁绕组接地保护存在的问题,从励磁电压变化、元件参数选取、交流分量等方面对乒乓式励磁绕组接地保护的测量精度进行了理论分析和仿真验证。实验结果表明:在桥臂电阻和测量电阻选取不同阻值时保护精度不同,励磁电压变化时保护的精度也相应变化。为了尽量减少交流分量的影响,采用傅里叶算法对测量值进行了滤波处理。仿真结果验证了理论分析的正确性,测量数据与测量精度满足实际需要。In view of the problem of current ping-pong-type of rotor earth fault protection,t his paper does theoretical analysis and simulation on its measuring accuracy from the the aspects of excitation voltage change,the components parameters selecting and AC components,etc.The experimental results show that the accuracy is different when the bridge arm resistance and measurement resistance are different,protection also changes accordingly in accuracy with excitation voltage changed.In order to minimize the impact of the AC component,Fourier algorithm is used to filter the measurements.The simulation results confirm the correctness of theoretical analysis.Measurement data and measurement accuracy can meet the actual demand.
分 类 号:TM862[电气工程—高电压与绝缘技术]