改进电气几何模型法在1000kV输电线路雷电绕击跳闸率计算中的应用  被引量:29

Application of Improved Electrical Geometry Model in Calculation of Lightning Shielding Failure-Caused Trip-out Rate of 1 000 kV Power Transmission Line

在线阅读下载全文

作  者:彭谦[1] 李军[1] 卞鹏[1] 康东升[1] 单志祥[2] 

机构地区:[1]国核电力规划设计研究院,北京市西城区100032 [2]中冶京诚工程技术有限公司,北京市大兴区100176

出  处:《电网技术》2010年第9期155-159,共5页Power System Technology

摘  要:分析现有3种输电线路雷电绕击计算方法的优缺点,改进了电气几何模型法。求解雷电流垂直地面入射时击距曲线间的交点坐标;根据雷电流入射角的变化,将交点映射到不同的几何空间;根据实际击距曲线修正交点坐标并求解雷电绕击跳闸率。计算结果表明,改进电气几何模型法较传统方法计算更为准确。最后,应用该方法分析了地线保护角和杆塔呼高、中相横担长度、层间距对1000 kV输电线路雷电绕击跳闸率的影响。Advantages and disadvantages of three existing methods to calculate lightning shielding failure are analyzed. The electrical geometry model method is improved to solve the coordinates of intersection point of striking distance curves while the incident direction of is perpendicular to ground; according to the change of incidence angle of lightning current, then the intersection point is mapped to different geometric spaces; and then based on actual striking distance curves the coordinates of intersection point are modified to solve the trip-out rate due to lightning shielding failure. Calculation results show that the improved electrical geometry model method is more accurate than traditional methods. Finally, applying the improved method the influences of ground wire protection angle, tower height, cross arm iength of middle phase and layer space on lightning shielding failure-caused trip-out rate of 1 000 kV power transmission line are analyzed.

关 键 词:电气几何模型 1000 KV输电线路 雷电绕击 

分 类 号:TM863[电气工程—高电压与绝缘技术]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象