天然气调压站安全评价与管理  被引量:5

Safety Evaluation and Management of Natural Gas Regulator Station

在线阅读下载全文

作  者:魏璠[1] 渠颖[2] 

机构地区:[1]天津城市建设学院能源与机械工程系,天津300384 [2]中国市政工程华北设计研究总院,天津300074

出  处:《煤气与热力》2010年第10期41-44,共4页Gas & Heat

摘  要:分析了导致天然气调压站泄漏造成火灾、爆炸的危险因素,遵循安全评价中事故最大化原则,以蒸气云爆炸为模型,对天然气泄漏火灾、爆炸的灾害后果进行了定量分析。在泄漏面积为1mm2的情况下,即使泄漏持续5min,四级损伤半径会达到6.62m。在工程的设计、施工及运行管理阶段要制定有针对性的安全措施并严格执行。The risk factors causing leakage at natural gas regulator station, resulting in fire and explosion, are analyzed. The consequences of fire and explosion from leakage of natural gas are quantitatively analyzed by vapor cloud explosion model according to the accident maximization principle in safety evaluation. Under the condition of leakage area of 1 mm2, the four-stage damage radius will reach 6.62 m even if the leakage lasts for 5 min. The safety measures must be established and strictly implemented the project design, construction and operation management.

关 键 词:调压站 泄漏 火灾 爆炸 安全评价 

分 类 号:TU996[建筑科学—供热、供燃气、通风及空调工程]

 