检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]华北电力大学电力系统保护与动态安全监控教育部重点实验室,河北保定071003 [2]浙江省电力建设有限公司,浙江宁波315000
出 处:《中国电力》2010年第11期26-30,共5页Electric Power
摘 要:根据变压器在空投和内部故障情况下等效瞬时励磁电感的波形差异性,提出一种利用波形相关性判别励磁涌流和故障电流的新方法。涌流时变压器铁芯必然经历饱和与非饱和过程,瞬时励磁电感是时变且交替变化的。内部故障时,变压器铁芯工作于线性区域,瞬时励磁电感恒为常数。在此基础上,提出利用波形对称度分析等效瞬时电感前后半个周期波形的对称性。通过涌流和故障时等效瞬时电感波形对称度的大小判别涌流和故障。动模试验分析结果表明,新方法能有效区分励磁涌流和故障电流,对轻微匝间故障也有足够的灵敏度。A new waveform symmetry algorithm for distinguishing the inrush and fault currents of power transformers was introduced based on the waveform differences of equivalent instantaneous inductance between unloading and internal faults. The cause of the inrush currents is that the saturation of core in the transformer and the equivalent instantaneous inductance varies alternately. When the transformer operates in the linear section of the magnetizing curve for the internal fault, the equivalent instantaneous inductance is constant. On this basis, a protective scheme was presented for distinguishing the inrush and fault currents by analyzing the symmetry degrees of pre and post half-waves of equivalent instantaneous inductance. The experimental results indicate that the proposed principle is also reliable and sensitive to slight turn-to-turn faults.