中压交联聚乙烯电缆接头人工缺陷局部放电特性  被引量:24

Partial Discharge Property of Artificial Defects at Medium Pressure Cross Linking Polyethylene Cables Joints

在线阅读下载全文

作  者:姜芸[1] 闵红[1] 罗俊华[2] 李海[1] 李文杰[2] 夏荣[2] 

机构地区:[1]上海市电力公司检修公司,上海200072 [2]国网电力科学研究院,武汉430074

出  处:《华东电力》2010年第10期1627-1629,共3页East China Electric Power

摘  要:中压交联聚乙烯(XLPE)电缆系统(电缆附件)故障,大多归因于生产制造和安装工艺不当导致的局部缺陷。介绍安装工艺不当导致的接头缺陷,并在试验室内实际制作了7种35 kV XLPE电缆接头人工缺陷,获取了其典型放电谱图,为在线检测放电谱图的诊断提供了缺陷样本数据。The faults of the medium voltage cross-linked polyethylene(XLPE) cable system(cable accessories) are mostly attributed to the partial defects caused by the production manufacturing and the improper installation technology.The joint defects caused by the improper installation technology were described,seven kinds of 35 kV XLPE joints artificial defects were made in the laboratory,and typical discharge maps were obtained.This provided the defects sample date for the diagnosis of the on-line detected the discharged map.

关 键 词:电缆 人工缺陷 局部放电 

分 类 号:TM247[一般工业技术—材料科学与工程]

 