一起线路与主变保护定值配合失当的事故分析  被引量:7

Analysis on the accident of mismatch between line and transformer protection setting

在线阅读下载全文

作  者:武万才[1] 聂会军[1] 边疆[1] 

机构地区:[1]宁夏电力公司吴忠供电局,宁夏吴忠751100

出  处:《电力系统保护与控制》2011年第2期149-151,154,共4页Power System Protection and Control

摘  要:介绍了宁夏电网红寺堡变一条110kV出线因鸟害造成的单相接地故障,从而导致该线路末端变电所主变零序过压保护误动作。通过结合实际保护定值对该故障进行了详细的分析,发现是由于电网中实际保护定值的配合失当,保护选择性和灵敏性不足引起的。在事故原因分析清楚后,通过对线路防鸟害、主变保护和线路保护定值校核整定方面提出了改进方案及对策。This paper introduces a single-phase grounding breakdown caused by a bird damage that occurs in the 110 kV line in Hongsipu substation of Ningxia Power Grid,which led to the wrong action of the line end main transformer zero-sequence overvoltage protection.Based upon the practical protection setting value situation,and by analyzing the accident in detail,we find that the weak selectivity and sensitivity of practical protection and the improper coordination of relay settings are the main reasons.After the reason is clear,aiming at the problems of bird damage and main transformer protection and line protection setting inspection,this paper puts forward the corresponding improvement scheme and countermeasure.

关 键 词:鸟害 跳闸 零序过压保护 定值 防范措施 

分 类 号:TM773[电气工程—电力系统及自动化]

 