电缆防火涂料阻火有效性试验  被引量:5

Efficiency of fire-retardant cable coating in cable tunnel fire test

在线阅读下载全文

作  者:李晓康[1,2] 杜文锋[2] 徐志胜[1] 

机构地区:[1]中南大学防灾科学与安全技术研究所,湖南长沙410075 [2]中国人民武装警察部队学院消防工程系,河北廊坊065000

出  处:《南京工业大学学报(自然科学版)》2011年第2期38-41,共4页Journal of Nanjing Tech University(Natural Science Edition)

摘  要:根据电缆隧道实际环境,建立电缆水平燃烧试验平台,研究不同火灾荷载和通风速度下,受防火涂料保护电缆延燃长度的变化规律。结果表明:一定风速条件下,电缆延燃长度随敷设宽度增加呈指数增长,可根据隧道内通风速度和电缆束宽度近似预测电缆延燃长度,从而为电缆隧道的防火设计提供依据。An experimental platform for horizontal combustion of cables was designed according to the tunnel environment,and the char length of cables covered with coating was investigated under different fire loads and ventilation conditions.The results showed that the char length grew exponentially with the cable laying width at a certain wind velocity and the length was predictable based on the ventilation and the width of bunched cables,thus it could provide the basis for the fire protection design of cable tunnels.

关 键 词:电缆隧道 防火涂料 延燃长度 通风速度 火灾荷载 

分 类 号:X932[环境科学与工程—安全科学]

 