作 者:施菁华[1] 秦庆芝[1] 帅群[2] 邓洪洲[2] 吴国强[3]
机构地区:[1]华北电力设计院工程有限公司,北京市100120 [2]同济大学建筑工程系,上海市200092 [3]中国电力科学研究院,北京市100192
出 处:《电力建设》2011年第4期29-33,共5页Electric Power Construction
基 金:国家电网公司钢管塔通用设计
摘 要:SZ2U钢管塔为使用Q460高强度钢材的1000kV同塔双回路直线型钢管真型塔,塔全高103.6m,单基塔质量132t。依据标准DL/T899—2004《架空线路杆塔结构荷载试验》,在正常大风、锚线、断线等8个试验工况下对其进行试验,试验结果表明:SZ2U钢管塔的位移测试结果满足变形要求,应变测试结果没有超过构件承载力,说明试验塔强度和刚度均符合设计要求,并有一定的安全储备;同时节点构造和法兰连接安全可靠。特高压输电钢管塔设计中采用Q460高强度钢材,既能满足设计要求,又能减轻塔重,建议在实际工程中试点应用。试验同时对输电钢管塔主材的次弯矩进行了真型塔测量,通过实际测量值与理论分析对比,得到输电钢管塔变坡处以下主材的次弯矩效应比较显著,建议工程中建立有限元模型进行强度校核,必要时采用考虑节点刚度的有限元模型。The SZ2U tubular steel tower,103.6 m in height and 132 tons in weight,and made of the Q460 high-strength steel,is a full-scale testing tower applied in 1 000 kV UHV AC double-circuit transmission line project.The test was carried out according to the standard DL/T 899—2004 "Loading Tests on Tower and Pole Structures of Overhead Line" under 8 different operation conditions,including wind,anchor-wire,broken wire,and so on.The testing results show that the actual displacement and stress of the tower SZ2U are within the limits of deformation and member's bearing capacity respectively;the strength and stiffness of the testing tower meet the design requirement with a certain safety margin,and the joint construction and flange connection are reliable.Application of the Q460 high-strength steel in UHV transmission tower design can not only meet the requirement of design code,but also reduces the weight of the transmission towers.It is therefore recommended to use it through pilot projects.In addition,the secondary moment of the tower's primary members is measured during the full-scale test.A comparison of the measured result and the theoretical values indicates that the effect of secondary moment of the primary members under the varying slope is prominent,and it is therefore recommended to establish the finite element model,the finite element model of node rigidity if necessity,to check the strength.
关 键 词:特高压双回路 钢管塔 Q460高强钢 真型试验 次应力 试验分析 工程建议
分 类 号:TM753[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.15