某工程实施地源热泵系统的可行性研究  被引量:2

The Feasible Research of Implementation on Ground-coupled Heat Pump System in one Project

在线阅读下载全文

作  者:高伟[1] 王厚华[1] 林真国[1] 

机构地区:[1]重庆大学城市建设与环境工程学院,重庆400045

出  处:《制冷与空调(四川)》2011年第2期186-190,共5页Refrigeration and Air Conditioning

摘  要:以某工程为例,对其全年吸放热不平衡率进行分析,并通过对两测试井进行夏季工况条件下的地埋管换热性能实验,得出夏季单位井深换热量为 108.5W/m,理论分析冬季单位井深换热量为57.1W/m,最后与常规空调系统进行经济性比较,最终论证该工程实施地源热泵方案的可行性。The annual suction exothermic unbalanced rate is analyzed with a project in this study, buried tube which is under the summer working conditions in two tests wells is tested for heat exchange performance, which obtains that heat exchange for deep unit in summer is 108.5 W/m. And heat exchange for deep unit in winter in theoretical analysis is 57.1 W/m. Finally, it is compared economically with conventional air conditioning system. Eventually, it is demonstrated that ground source heat pump scheme for the project is feasible.

关 键 词:地源热泵 不平衡率 单位井深换热量 可行性分析 

分 类 号:TU83[建筑科学—供热、供燃气、通风及空调工程]

 