检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:黄兴泉[1] 郭琳[2] 李成榕[1] 刘树春[1]
机构地区:[1]华北电力大学,北京100085 [2]郑州电力高等专科学校,河南郑州450004
出 处:《华北电力大学学报(自然科学版)》1999年第4期1-5,共5页Journal of North China Electric Power University:Natural Science Edition
摘 要:X射线照射绝缘介质,可以激发或加强介质中的气隙放电;调节X射线照射的方位并检测因射线激励所产生的局部放电信号,可有效地确定局部放电的部位。本文通过研究X射线激励对变压器模型中气隙放电的影响,探讨X射线激励下的局部放电定位,为X射线激励下局部放电测量和定位技术在油纸绝缘系统中的应用奠定基础。There are some defects existing in the power transformers such as manufacture craft and insulationdeterioration. To this end, partial discharge tests are often performed as a final check on quality. With conventional PD measurement technique, PD detection sensitivity is often limited by the availability of electrons necessary to initiate PD in defects. Statistical time lag, i. e., the time required for a discharge initiating free electronto appear in the defect, could make a dangerous defect undetectable. The application of X-rays during electricalPD measurements can increase the free electron production rate in the cavity and decrease the statistical time lag,resulting in an improved PD sensitivity. Partial discharge is induced or intensified when dielectric is irradiatedby X-ray, the location of partial discharge can been fixed on by modulating orientation of X-ray irradiation anddetecting partial discharge signal because of X-ray irradiation.
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.28