葛洲坝换流站直流滤波器中电流互感器损坏事故分析计算及对策  被引量:2

ANALYSIS, CALCULATION AND COUNTERMEASURES OF CURRENT TRANSFORMER DAMAGE IN DC FILTER OF GEZHOUBA CONVERTER STATION

在线阅读下载全文

作  者:张致[1] 文凯成[1] 彭晓莺[1] 涂明 

机构地区:[1]湖北省电力试验研究所,武汉市430077 [2]湖北省电力局生产处,武汉市430077

出  处:《电网技术》1999年第11期67-70,共4页Power System Technology

摘  要:葛洲坝换流站连续两次在雷雨天气中发生直流滤波器中电流互感器损坏事故。文章综述了对损坏设备的分解,过电压计算及分析,并提出了在12/36 次谐波滤波器处改用220kV 电流互感器,在12/24 次谐波滤波器处加220kV 电压等级避雷器作相应保护的对策。In thunderstorm two of the current transformers in Gezhouba converter station were damaged one after another. The disassembly, inspection, overvoltage calculation and analysis of the damaged CTs are summarized. It is put forward that in the place where the 12/36th harmonic filters are installed the filters should be replaced by 220kV CTs, and in the place where the 12/24th harmonic filters are installed the 220kV lightning arresters should be added. The operational experience shows that the above mentioned protective countermeasures are successful.

关 键 词:直流滤波器 电流互感器 雷击 损坏 换流站 

分 类 号:TM63[电气工程—电力系统及自动化] TM452.07

 