检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:王为国[1] 尹项根[1] 余江[1] 段献忠[1] 陈德树[1]
出 处:《电力系统自动化》1999年第20期9-11,共3页Automation of Electric Power Systems
基 金:国家自然科学基金!59637050;国家教委跨世纪优秀人才培养计划基金
摘 要:可控串联电容补偿(TCSC)动态基频阻抗特性对距离保护的影响与固定串联电容补偿(FSC)对距离保护的影响在主要方面是相似的,电压反向及电压互感器、电流互感器位置的选择同样是影响保护性能的关键因素,但电压反向、动态特性的变化、保护范围及动作速度等方面也存在差别。在FSC线路上能运行的距离保护在TCSC线路上仍然能很好地运行。The influence of TCSC dynamic power frequency impedance on distance protection relay is similar to that of FSC.Voltage inversion and location of potential transformer and current transformer are also the key factors for TCSC to influence the performance of distance protection relay. But there still exist some differences between TCSC and FSC about voltage inversion, variation of dynamic characteristic. protection range and tripping time. The distance relays with good per formance on transmission lines with FSC will also have good performance on lines with TCSC.
关 键 词:TCSC 动态基频阻抗 距离保护 输电线路 继电保护
分 类 号:TM773[电气工程—电力系统及自动化]