基于实际雷电参数的10kV架空绝缘线路防雷分析  被引量:4

Lightning Protection Analysis of The 10kV Overhead Insulation Line Based on Real Lightning Parameters

在线阅读下载全文

作  者:何建林[1] 张电[1] 刘渝根[2] 田金虎[3] 

机构地区:[1]重庆市电力公司江北供电局,重庆401147 [2]重庆大学输配电装备及系统安全与新技术国家重点实验室,重庆400044 [3]重庆市电力公司检修分公司,重庆400039

出  处:《重庆电力高等专科学校学报》2011年第2期68-72,共5页Journal of Chongqing Electric Power College

摘  要:依托雷电定位系统(LLS)收集雷电参数,分析计算感应雷作用下正、负极性落雷时10kV架空绝缘配电线路雷击闪络率,并与实际线路雷击跳闸情况进行比较分析。提出综合考虑运用支柱绝缘子配合穿刺型防弧金具、串联外间隙氧化锌避雷器来提高10kV架空绝缘线路耐雷水平,防止雷击断线。Based on the LLS,the lightning parameters were collected.The flashover rates of the 10kV overhead insulation line caused by inductive overvoltage from positive and negative lightning were calculated.Then,the flashover rates and the statistical lightning trip-out rates of the line were analyzed in a comparative way.This essay proposes that the pillar insulator with arc-protection hardware with stabs and the metal oxide surge arrester with series gaps be used appropriately to improve the lightning resistance of the 10kV line and prevent lightning breaks.

关 键 词:架空绝缘导线 雷电参数 防雷措施 

分 类 号:TM863[电气工程—高电压与绝缘技术]

 