变蒸发温度下压缩冷凝机组的性能实验研究  被引量:5

Experiments Study on Performance of Condensing Unit at Varied Evaporating Temperature

在线阅读下载全文

作  者:张进贤[1] 黄虎[1] 黄芳[2] 张忠斌[1] 汪庆 

机构地区:[1]南京师范大学能源与机械工程学院,江苏南京210042 [2]衡水科技学校,河北衡水053000 [3]泰州市南风冷链有限公司,江苏泰州225300

出  处:《南京师范大学学报(工程技术版)》2011年第2期58-61,共4页Journal of Nanjing Normal University(Engineering and Technology Edition)

摘  要:保持环境温度不变,在-15℃~0℃的蒸发温度范围内对压缩冷凝机组进行了测试.分析了变蒸发温度对压缩冷凝机组COP、输入功率、压力比、吸气温度、排气温度等性能参数的影响,得出制冷量和蒸发温度之间的线性拟合关系.由实验得出:环境温度不变,蒸发温度上升1℃,COP平均上升2.2%.该实验为压缩冷凝机组的设计和工程应用提供了实验参考依据.Experiment of condensing unit at varied evaporating temperature has been conducted when the ambient temperature is constant.The effects of the evaporating temperature on the characteristics of COP,power input,compression ratio were analyzed.The linearl fitting relation between refrigerated volume and the evaporating temperature was obtained.The test shows that with an increase in the evaporating temperature of 1℃,COP increased by 2.2% when the ambient temperature is constant.The test provides an important experimental reference for further improvement and application.

关 键 词:变蒸发温度 压缩冷凝机组 性能 试验 

分 类 号:TU834[建筑科学—供热、供燃气、通风及空调工程]

 