失稳故障支路拟裕度评估及控制的虚拟支路法  

A virtual branch method of quasi-margin evaluation and control for instable fault branch

在线阅读下载全文

作  者:苗峰显[1] 刘庆杰[2] 

机构地区:[1]国家电网公司交流建设分公司,北京100052 [2]中国科学院对地观测与数字地球科学中心,北京100094

出  处:《中国电力》2011年第7期1-5,共5页Electric Power

摘  要:为评估失稳故障支路的严重程度及解决故障后系统失去潮流可行解的问题,提出了失稳故障支路拟裕度评估及控制的虚拟支路法。该方法将待切除的故障支路用一条含参数的虚拟支路置换,使虚拟支路开断问题转换为故障支路两端点注入功率增长的裕度问题,并用拟裕度大小评估故障支路的严重程度。算法利用最小控制代价的过程控制法,使虚拟支路完全切除后系统获得可行潮流解;故障后优化控制是在可行解上优化系统,以满足稳定裕度要求。通过IEEE算例验证了方法的可行性和有效性。A virtual branch quasi-margin evaluation and control method is proposed to evaluate the severity of instable fault branches. The proposed method has the ability to overcome the problem that no feasible power flow solution existed after faults in the system. This method replaces the fault branch with a parameterized virtual branch, and changes the removed virtual branch issue to the problem of the injected power in fault branch. The quasi-margin is used for evaluating the severity of fault branch. Based on process control with minimum control cost objective, feasible power flow solution can be obtained. The post-fauh optimal stability control is based on feasible power flow solution. The feasibility and efficiency of proposed method are validated by the simulation results of IEEE testing system.

关 键 词:电压稳定与控制 置换定理 支路故障 灵敏度 连续潮流 

分 类 号:TM711[电气工程—电力系统及自动化]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象