风电场接入系统继电保护的配置与整定  被引量:4

Configuration and Setting of Relay Protection for Wind Farm Integration System

在线阅读下载全文

作  者:李斌[1] 王琦 隆贤林[1] 

机构地区:[1]南京工程学院,南京211167 [2]吉林龙源风力发电有限公司,长春130021

出  处:《吉林电力》2011年第4期29-33,共5页Jilin Electric Power

基  金:南京工程学院科研基金项目(121101090304)

摘  要:针对风电场接入系统联络线与风电场变压器的继电保护配置与整定,分析了风力发电机有无低电压穿越(LVRT)功能对保护配置与整定的影响,并利用M ATLAB/S im u link软件仿真了具有LVRT功能风力发电机组的短路电流。仿真结果表明,低电压穿越有助于提高快速保护的灵敏度,但也增加了后备保护配置的复杂度,因此,合理的保护配置与整定值有利于保证系统的安全。In this paper, the authors analyzed the protection's configuration and settings of interconnection line and transformers in wind farm. On base of this, it discussed the influence of wind power generator with LVRT (low voltage ride through) or not. It also constructed simulation module of generator with LVRT to obtain short-circuit current by MATLAB/Simulink. As a result, it would increase sensitivity of main relays, however it increased complexity of backup protections, to assure grid's security, it must adopt appropriate protection's configuration and settings.

关 键 词:继电保护配置 整定 风电场 低电压穿越 仿真 

分 类 号:TM774[电气工程—电力系统及自动化]

 