碳纤维布抗弯加固混凝土梁的火灾行为  被引量:8

FIRE BEHAVIORS OF CONCRETE BEAMS STRENGTHENED WITH CARBON FIBER SHEET

在线阅读下载全文

作  者:刘汾涛[1,2] 吴波[1,3] 魏德敏[1] 

机构地区:[1]华南理工大学亚热带建筑科学国家重点实验室,广州510640 [2]广东水利电力职业技术学院,广州510635 [3]上海建科院上海市工程结构新技术重点实验室,上海200032

出  处:《工程力学》2011年第9期72-78,共7页Engineering Mechanics

基  金:十一五国家科技支撑计划子课题项目(2006BAJ03A03-12);国家自然科学基金项目(51025829;50738005);教育部科学技术研究重点项目(108106);教育部博士学科点专项科研基金项目(20060561014);上海市工程结构新技术重点实验室开放课题项目(2010-KF01)

摘  要:对4根碳纤维布抗弯加固混凝土梁和1根未加固对比梁进行了明火试验,前者碳纤维布表面涂抹有非膨胀型防火涂料。试验考察了梁跨中裂缝对受拉钢筋温度的影响,以及防火涂料厚度相对较薄时加固梁的破坏形态、高温变形和耐火极限。试验结果表明:1)加固梁在达到耐火极限之前相当长一段时间内的挠度及裂缝宽度和深度较小,跨中裂缝对受拉钢筋温度影响有限;2)梁底混凝土的爆裂脱落可使加固梁的高温破坏位置发生显著改变;3)在实际荷载比不大于0.5的情况下,即使防火涂料厚度较薄(10mm~20mm),加固梁仍可达到2h一级耐火要求。Test results of five concrete beams in fire are presented in this paper, four of which were strengthened with carbon fiber sheet and protected by passive fire insulation, and the other un-strengthened one was tested as a comparison. The primary objectives of these tests are to investigate the influence of flexural cracks at mid span on the temperatures of tensile reinforcements, and to evaluate the failure mode, deformation and fire resistance of the strengthened beams with relatively thin fire insulation. Test results show that: (a) the deflection and crack width and depth of the beam increase very slowly for a long duration of the fire, as a result, the effect of flexural cracks at mid span on the temperatures of tensile rebars is very limited; (b) spalling and debonding of concrete at beam soffit may cause a change of the failure location of the strengthened beam in fire; and (c) in the case that the actual load ratio is not larger than 0.5, the fire endurance of a strengthened beam with relatively thin fire insulation (e.g., 10 mm-20 mm) can meet the requirement of 2h in design code.

关 键 词:碳纤维布 混凝土梁 火灾行为 试验 裂缝 

分 类 号:TU375.1[建筑科学—结构工程]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象