基于ATP-EMTP的耐雷水平研究  被引量:38

Study on Lightning Withstand Level Based on AT-EMTP

在线阅读下载全文

作  者:陈冬[1] 刘建华[1] 贾晨曦[1] 

机构地区:[1]中国矿业大学信息与电气工程学院.江苏徐州221008

出  处:《电瓷避雷器》2011年第5期8-11,15,共5页Insulators and Surge Arresters

摘  要:采用ATP-EMTP软件搭建某实际线路模型,通过规程计算与仿真计算,对比分析3种雷击方式下的耐雷水平,研究哪种情况对线路的危害最大。针对雷击塔顶这种方式下,仿真分析其变量对耐雷水平的影响程度。并分析规程计算与仿真计算耐雷水平时产生误差的原因。认为:在对线路采取防雷措施时应特别考虑雷击塔顶这种情况并首先应将各基杆塔的接地电阻降至标准值以下。A model of real lines is built with ATP-EMTP, and through schedule calculation and simulation calculation, three lightning ways of withstand level are contrasted and analyzed, and it is studied that which is the most damaging situation to the line. And for the way of lightning stroke to tower top, the impact of variables on lightning withstand level is simulated and analyzed. Then the reason of inaccuracy during schedule calculation and simulation calculation is analyzed. It is considered that, that the way of lightning stroke to tower top must be considered especially when taking measures of lightning protection to lines and should reduce earth resistance of each tower under the standard value firstly.

关 键 词:耐雷水平 ATP-EMTP 绕击 

分 类 号:TM862[电气工程—高电压与绝缘技术]

 