TA深度饱和及变比选择问题的探讨  

Study on the deep-saturation of TA and transformation ratio selection

在线阅读下载全文

作  者:梅姚[1] 陈新[1] 赵毅[1] 王春光[1] 陈文彬[1] 

机构地区:[1]甘肃电力调度通信中心

出  处:《科技致富向导》2011年第35期315-315,314,共2页Guide of Sci-tech Magazine

摘  要:由于系统容量增大或系统结构等原因,高压变电所10~35kV侧出线在近处短路时出现的特大电流,大大超过了电流互感器(TA)的10%误差曲线所容许的电流倍数,严重影响保护装置正确动作。文中对某110kV变电站10kV线路出口发生三相短路,TA深度饱和致使保护装置未能快速动作的事故进行了分析,并就特大电流下TA深度饱和对微机保护的影响及TA变比的选择提出了意见。Based on capacity increase or structure change of the power system, an extra-high current may appear in 35kV orl0kV outlet of high voltage substations when a short-circuit fault happens nearby. It greatly exceeds the permitted value of 10% error curve of protection current transformer (TA) and affects the performance of relevant protect equipment. A fault that fast action failure of protection caused by deep-saturation of TA when three-phase short circuit occurs on the 10 kV outlet of a ll0kV substation is analyzed. Also the influence of TA deep-saturation on relay protection device, and the suggestions of transformation ratio selection are presented.

关 键 词:电流互感器(TA) 深度饱和 变比 继电保护 

分 类 号:TM452[电气工程—电器]

 