阻抗匹配平衡变压器电能质量评估计算的匝数比分析  

Analysis on Turn Ratio on Assessment and Calculation on Power Quality of Impedance-matching Balance Transformer

在线阅读下载全文

作  者:周天晖[1] 胡加泉[2] 

机构地区:[1]江西省电力科学研究院,江西南昌330096 [2]江西省电力公司,江西南昌330077

出  处:《广东电力》2011年第11期96-99,共4页Guangdong Electric Power

摘  要:针对阻抗匹配平衡变压器结构因与电力系统传统使用的三相变压器结构不同而导致的对匝数比取值问题的误解,通过对阻抗匹配平衡变压器接线方式、绕阻布置、阻抗设计等方面的分析,得出其匝数比应取槡8,并分析了匝数比取值缪误对牵引变电站接入电网的电能质量评估的影响。Aiming at misconception of turn ratio value caused by structural difference between impedance-matching balance transformer and conventional three phase transformer, the paper analyzes wiring mode, winding configuration, impedance design of impedance-matching balance transformer. It is concluded that the turn ratio should be √8 rather than 4, and the paper also analyzes impact of wrong value of turn ratio on assessment of power quality of gird-connected traction substation.

关 键 词:阻抗匹配平衡变压器 电能质量评估 匝数比 

分 类 号:TM922.73[电气工程—电力电子与电力传动]

 