发电机低励失磁保护Ⅲ段误动原因分析和预防措施  被引量:1

Analysis on reasons of incorrect tripping of excitation-loss protection section III of generator and preventive measures

在线阅读下载全文

作  者:王绍平 

机构地区:[1]华电四川发电有限责任公司攀枝花分公司,四川攀枝花617065

出  处:《华电技术》2012年第1期10-11,15,共3页HUADIAN TECHNOLOGY

摘  要:针对发电机失磁保护Ⅲ段保护误动事故比较多的情况,对发电机失磁保护Ⅲ段保护跳闸原因进行了分析,失磁保护误动作的原因是失磁保护Ⅲ段外部系统电压开入量在机组方式发生改变后,未能及时改变保护接线方式。提出了防止失磁保护误动作的预防措施,以确保设备安全运行。The incorrect tripping accident of the excitation-loss protection section III for the generator was occurred frequently.The reasons of the incorrect tripping of the excitation-loss protection section III of the generator were analyzed.According the analysis,the reason of the incorrect tripping of excitation-loss protection is that the operation mode of the unit primary system had been changed,but the binary input connection of excitation loss protection section III did not be modified relevantly.The measures to prevent incorrect tripping of excitation-loss protection were put forward,which are helpful for ensuring the safe operation of the devices.

关 键 词:发电机 低励失磁Ⅲ段 误动原因 分析 预防措施 

分 类 号:TK267[动力工程及工程热物理—动力机械及工程]

 