检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]华北电力设计院工程有限公司,北京市100120
出 处:《电力建设》2012年第2期67-70,共4页Electric Power Construction
摘 要:基于多个SCAL型间接空冷系统的工程设计,分析了初始温差(initial temperature difference,ITD)、迎面风速、散热器高度、塔形尺寸等设计参数对空冷系统规模的影响。进行了SCAL型间接空冷系统设计规模的优化计算,包括ITD值的优化、散热器高度的优化、迎面风速的优化计算,讨论了其他设计参数的选取,提出空冷电厂年运行费用的计算方法,给出指导SCAL型间接空冷系统设计参数优化的原则。Based on engineering designs of SCAL-type indirect air-cooling system for several power projects,the effect of design parameters on the air-cooling system scale are analyzed such as initial temperature difference(ITD),face velocity,radiator height,and size of cooling tower etc.In addition,the optimized calculation of the design scale for SCAL-type indirect air-cooling system are carried out,including that of ITD,face velocity and radiator height,while the choices of other design parameters are discussed.Furthermore,the method for calculating annual operation cost of air-cooling power plant and the engineering optimization design principle of the SCAL-type indirect air-cooling system are put forward.
关 键 词:SCAL型间接空冷系统 初始温差(ITD) 迎面风速 散热器高度 优化
分 类 号:TM621.7[电气工程—电力系统及自动化]