焦化废水回用于循环冷却水的研究  被引量:1

Study of Coking Wastewater Used in Cooling Water Circulation

在线阅读下载全文

作  者:费卓越[1] 单明军[1] 寇丽红 赵先奕[1] 

机构地区:[1]辽宁科技大学,辽宁鞍山114044 [2]辽宁清澄环境工程有限公司,辽宁鞍山114051

出  处:《绿色科技》2012年第2期102-104,共3页Journal of Green Science and Technology

摘  要:研究了不同种类缓蚀、阻垢药剂对焦化废水深度处理后出水的缓蚀阻垢效果,并对缓蚀、阻垢药剂进行了复配实验。结果表明:选用浓度为4mg/L的HEDP作为缓蚀剂,浓度为5mg/L的HB-901为阻垢剂,复配后进行焦化废水深度处理后的缓蚀、阻垢,腐蚀率为0.0291mm/年,低于《工业循环冷却水处理设计规范》(GB50050-95)中0.125mm/年的要求,可满足回用于循环冷却水补水系统中的水质要求。This paper studies the effects of the different kinds of corrosion and scale inhibitor on coking wastewater which has been deeply treated, and carries out the pharmaceutical compound experiment.The results show that when HEDP with the concentration of 4mg/L was used as a corrosion inhibitor and HB-901 with the concentration of 5mg/L as scale inhibitor, corrosion rate of coking wastewater which had been deeply treated was 0.0291mm/a, which is much lower than 0.125 mm/a that is the limit of allowed corrosion rate specified in' code for design of industrial recirculating cooling water treatment '(GB50050-95) , so it can meet the water quality requirements of makeup water for circulatory cooling water system.

关 键 词:焦化废水 缓蚀阻垢 实验研究 循环冷却水 

分 类 号:X73[环境科学与工程—环境工程]

 