风电场无功分层配置的思考与例证  被引量:2

Analysis and Site Trial on Hierarchical Control of Reactive Power in Wind Farms

在线阅读下载全文

作  者:闫忠平 刘平[2] 黄天啸[2] 雷为民 梁玉枝[2] 王丰[2] 

机构地区:[1]国网新源张家口风光储示范电站有限公司,河北张家口075000 [2]华北电力科学研究院有限责任公司,北京100045

出  处:《华北电力技术》2012年第3期1-3,10,共4页North China Electric Power

摘  要:目前并网的风机几乎都长期运行在功率因数为1的方式下,由升压站的无功补偿设备对风机箱变、集电线路、升压变及并网线路的无功损耗进行补偿。这种运行方式不仅与无功分层平衡就地补偿的原则不符,也对风机机端电压的调整不利,在故障情况下还会扩大风机脱网的规模。本文从现场调试的试验结果出发,根据实例提出了风电场的无功补偿主要来自风机发出无功功率的补偿方式,符合无功分层平衡就地补偿的原则,而且有利于风机机端电压的调整,在故障情况下还能避免无功潮流对电网的冲击,减小风机脱网的规模。Most grid-connected wind turbines nowadays are operating in a unity power factor mode. Reactive power loss of box transformer substations and feeders are compensated in step-up substation to meet the requirement of reac- tive power balance in wind farm transmission line. This operation mode doesn't comply with the principle that reactive power should balance in local. And it is not conductive to voltage adjustment of wind turbine. In some serious condi- tion,this would lead to more wind turbines disconnection from grid. This paper analyzed some site trials of wind tur- bines and drew a conclusion that wind turbines should generate reactive power as well as active power, compensating reactive power loss of box transformer substations and feeders instead of compensators in step-up substation. This op- eration mode is conductive to local reactive power balance principle and helpful to voltage control of wind turbines. Moreover, in serious fault condition, it would help line voltage to keep steady and avoid wind turbines from drop-off.

关 键 词:风力发电 无功调节 电压支撑 脱网 

分 类 号:TM614[电气工程—电力系统及自动化]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象